Standard_Drives_Guide

AF-650 GP General Purpose Drive Basic Wiring Diagrams

91 (L1) 92 (L2) 93 (L3)

(U) 96 (V) 97 (W) 98

3 Phase Input Power

(PE) 99

95

PE

Motor

Switch Mode Power Supply

DC Bus †

88 (-) 89 (+)

Dynamic Brake resistor

10Vdc 15mA 130/200mA + - + - 24Vdc

(R+) 82

50 (+10 V OUT)

+10Vdc

(R-) 81

S201

1 2

53 (A IN)

ON

0-10Vdc 0/4-20 mA

relay 1

ON=0-20mA OFF=0-10V

S202

03

ON

54 (A IN)

240Vac, 2A

0-10Vdc

21

02

0/4-20 mA

55 (COM A IN)

01

relay 2

AF-650 GP General Purpose Drive

12 (+24V OUT)

06

240Vac, 2A

13 (+24V OUT)

05

400Vac, 2A

Start*

24V (NPN) 0V (PNP) 0V (PNP) 24V (NPN)

04

18 (D IN)

No Operation*

Analog Output

19 (D IN)

(COM A OUT) 39

0/4-20 mA

(A OUT) 42

20 (COM D IN)

No Operation**

24V (NPN) 0V (PNP)

27

S801

(D IN/OUT)

ON = Terminated OFF = Open

24V

ON

21

0V

5V

Jog*

0V (PNP) 24V (NPN)

29

(D IN/OUT)

24V

0V

S801

0V

RS-485 Interface

RS-485

(P RS-485) 68

No Operation*

24V (NPN) 0V (PNP) 0V (PNP) 24V (NPN)

32 (D IN)

(N RS-485) 69

No Operation*

(COM RS-485) 61

33 (D IN)

(PNP) = Source (NPN) = Sink

Safe Stop Alarm*

37 (D IN)

* Indicates default setting; see Parameter Group E-## to re-program.

** Indicates default setting for version 1.10 drives or higher. Prior versions are set to Coast Inverse, indicating that terminal #27 must be Logic “High” to enable the drive to run. See Parameter E-03 Terminal 27 Digital Input to re-program. † These terminals are only available with optional factory installed brake chopper.